Billable shown in copper where the meter recorded under 85% of generation — meter fault or curtailment.
| Plant | Active | Generated | To grid | Peak | Yield kWh/kWp | PR | ₹ gen | ₹ billable |
|---|---|---|---|---|---|---|---|---|
| Jamnadas3,430 kWp est | 8/8 | 14,219 kWh | 14,060 | 2,319 kW | 4.15 | — | ₹56,874 | ₹56,240 |
| White Lotus2,910 kWp est | 8/8 | 13,843 kWh | 13,764 | 2,057 kW | 4.76 | — | ₹55,371 | ₹55,055 |
| Helium5,700 kWp est | 14/14 | 12,381 kWh | 12,019 | 2,777 kW | 2.17 | 0.665 | ₹49,524 | ₹48,075 |
| Madhav1,460 kWp est | 4/4 | 6,620 kWh | 6,573 | 1,013 kW | 4.53 | 0.747 | ₹26,479 | ₹26,291 |
| Aamantran1,090 kWp est | 0/3 | — kWh | no meter | — kW | — | — | ₹0 | — |
| Arogya1,120 kWp est | 0/3 | — kWh | no meter | — kW | — | — | ₹0 | — |
| Kanhaiya1,080 kWp est | 0/3 | — kWh | no meter | — kW | — | — | ₹0 | — |
| Kiran5,100 kWp est | 0/14 | — kWh | no meter | — kW | — | — | ₹0 | — |
| Murliwala1,080 kWp est | 0/3 | — kWh | no meter | — kW | — | — | ₹0 | — |
| Ravani1,090 kWp est | 0/3 | — kWh | no meter | — kW | — | — | ₹0 | — |
| Roopwada4,370 kWp est | 0/12 | — kWh | no meter | — kW | — | — | ₹0 | — |
Opened on this day, plus anything still open. Dead strings: Jamnadas_INV01 (5), Jamnadas_INV02 (2), Jamnadas_INV04 (5), Jamnadas_INV05 (3), Jamnadas_INV07 (4).
| Severity | Type | Message | Status |
|---|---|---|---|
| CRITICAL | DEVICE_OFFLINE | Arogya_INV01 silent for 172.5 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV05 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV04 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV03 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV02 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV01 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Murliwala_MFM01 silent for 173.6 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Murliwala_INV01 silent for 173.4 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Arogya_MFM01 silent for 172.4 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV06 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV07 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV08 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV09 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV10 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV11 silent for 630.2 h | CLEARED |
| CRITICAL | DEVICE_OFFLINE | Roopwada_INV12 silent for 630.2 h | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Jamnadas_INV01 reporting but generating 0 kW while fleet produces 3507 kW | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV02 silent for 49 min | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV03 silent for 49 min | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV04 silent for 49 min | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV01 silent for 49 min | CLEARED |
| WARNING | GRID_ANOMALY | Helium: meter recorded 82% of generation today (3994 of 4860 kWh) — meter fault or curtailment | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV09 reporting but generating 0 kW while fleet produces 5210 kW | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV04 silent for 63 min | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV02 silent for 63 min | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV01 silent for 63 min | CLEARED |
| WARNING | DEVICE_OFFLINE | Madhav_INV03 silent for 63 min | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV02 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV03 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV04 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV05 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV06 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV07 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV08 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV09 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV10 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV11 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV12 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV13 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |
| WARNING | ZERO_GENERATION_DAYTIME | Helium_INV14 reporting but generating 0 kW while fleet produces 3926 kW | CLEARED |